dc.identifier.citationMontenegro Benalcázar, Verónica Estefanía. (2017). Rediseño de la planta potabilizadora de agua para consumo humano en el Terminal de Productos Limpios (EP-PETROECUADOR), cantón Riobamba, provincia de Chimborazo. Escuela Superior Politécnica de Chimborazo. Riobamba.es_ES
dc.identifier.urihttp://dspace.espoch.edu.ec/handle/123456789/6629-
dc.descriptionEl presente trabajo consistió en el rediseño de un sistema de tratamiento de agua potable del Terminal de Productos Limpios de la Empresa Pública de Hidrocarburos PETROECUADOR, ubicada en el cantón Riobamba, provincia de Chimborazo, con el fin de obtener un recurso hídrico de calidad y que cumpla con los requisitos para consumo humano. Se inició con el muestreo y análisis fisicoquímicos y microbiológicos preliminares del agua basados en los Métodos Estándar, en el Laboratorio de Control de Calidad del Sistema de Tratamiento de Agua Potable “CHAQUISHCA”; los resultados indicaron que los parámetros fuera de norma son: Turbiedad con 5,37 unidades nefelométricas de turbiedad (NTU); Nitritos con 0,007 mg/L; Fosfatos con 0,71 mg/L; Hierro Total con 0,5 mg/L; Manganeso con 0,498 mg/L; Dureza Total con 357,2 mg/L; Coliformes Totales con 55 NMP/100 mL, y coliformes fecales con 15 NMP/100 mL. Se realizaron pruebas de tratabilidad que permitieron determinar la dosis de Policloruro de Aluminio (PAC) de 15 ppm con un auxiliar aniónico CHEMFLOC 6 ppm, concentración necesaria para disminuir los valores del parámetro Turbiedad, además se utilizó Hipoclorito de Calcio (HTH), con una concentración de 1 ppm para eliminar los contaminantes microbiológicos. Se concluyó con la propuesta de rediseño la misma que constará de un sistema de aireación, seguido por un sedimentador de tasa alta, un filtro grueso, un filtro lento descendente, dos filtros ablandadores, y finalmente el tanque de desinfección. Las pruebas de validación del tratamiento propuesto señalan que se obtendrá una remoción del 92,80% en turbiedad; 78,87% en fosfatos; 84,00% en hierro; 98,19% en manganeso; 88,24% en dureza; mientras que los coliformes fecales, totales y los nitritos son removidos completamente. Se recomienda cumplir con el manual de operación y mantenimiento para conservar las estructuras.es_ES
dc.description.abstractThe present work consisted on the redesign of a drinking water treatment system at the Clean Products Terminal of the Public Petroleum Company PETROECUADOR, located in Riobamba canton, Chimborazo province, in order to obtain a quality water resource that complies with the requirements for human consumption. It began with the sampling the preliminary microbiological, physicochemical and microbiological analyzes of the water based on the Standard Methods at the Laboratory of Quality Control of the System of Drinking Water Treatment “CHAQUISHCA”; the results indicated that the non-standard parameters are: Turbidity with 5,37 nephelometric turbidity units (NTU); Nitrites with 0,007 mg/L; Phosphates with 0,71 mg/L; Total Iron with 0,5 mg/L; Manganese with 0,498 mg/L; Total Hardness with 357,2 mg/L; Total coliforms with 55 NMP/100 mL, and fecal coliforms with 15 NMP/100 mL. Treatability test were carried out to the 15 ppm Aluminum Polychloride (APC) dose with an anionic auxiliary CHEMFLOC 6 ppm, concentration required to decrease Turbidity values, Calcium Hypochlorite (HTH) was also used, with a concentration of 1 ppm to eliminate microbiological contaminants. It was concluded with the redesign, it will consist of an aeration system, followed by a high rate sedimentation unit, a coarse filter, a slow descending filter, two softening filters, and finally the disinfection tank. The validation tests of the proposed treatment indicate that a removal of 92,80% in turbidity is obtained; 78,87% in phosphates; 84,00% in iron; 98,19% in manganese; 88,24% in hardness; while total fecal coliforms, and nitrites are completely removed. It is recommended to comply with the operation and maintenance manual to conserve the structures.es_ES
dc.language.isospaes_ES
dc.publisherEscuela Superior Politécnica de Chimborazoes_ES
dc.relation.ispartofseriesUDCTFC;236T0260-
dc.subjectTECNOLOGÍA Y CIENCIAS DE LA INGENIERÍAes_ES
dc.subjectBIOTECNOLOGÍAes_ES
dc.subjectMEDIO AMBIENTEes_ES
dc.subjectMÉTODOS ESTÁNDARes_ES
dc.subjectAUXILIAR ANIÓNICO (CHEMFLOC)es_ES
dc.subjectPOLICLORURO DE ALUMINIO (PAC)es_ES
dc.subjectHIPOCLORITO DE CALCIO (HTH)es_ES
dc.titleRediseño de la planta potabilizadora de agua para consumo humano en el Terminal de Productos Limpios (EP-PETROECUADOR), cantón Riobamba, provincia de Chimborazo.es_ES
dc.typebachelorThesises_ES
dc.contributor.miembrotribunalCarrera Beltrán, Lourdes Cumandá-
Aparece en las colecciones: Ingeniero/a en Biotecnología Ambiental; Ingeniero/a Ambiental

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
236T0260.PDF6,55 MBAdobe PDFVista previa
Visualizar/Abrir


Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.