Por favor, use este identificador para citar o enlazar este ítem: http://dspace.espoch.edu.ec/handle/123456789/6211
Registro completo de metadatos
Campo DC Valor Lengua/Idioma
dc.contributor.advisorRivera Castillo, María Fernanda-
dc.contributor.authorZambrano Vallejo, Silvana Gabriela-
dc.date.accessioned2017-04-19T19:07:43Z-
dc.date.available2017-04-19T19:07:43Z-
dc.date.issued2016-10-
dc.identifier.citationZambrano Vallejo, Silvana Gabriela. (2016). Rediseño de la planta de tratamiento de agua potable para la parroquia Linares, cantón El Chaco. Escuela Superior Politécnica de Chimborazo. Riobamba.es_ES
dc.identifier.urihttp://dspace.espoch.edu.ec/handle/123456789/6211-
dc.descriptionEsta investigación tuvo como objetivo rediseñar el Sistema de Tratamiento de Agua Potable de la Parroquia Linares, Cantón El Chaco, para mejorar la calidad del agua y vida de la población. Se realizó una inspección del actual sistema de tratamiento, con la finalidad de identificar las potenciales fallas del sistema, posteriormente se realizó una caracterización físico, química y microbiológica, mediante un muestreo simple, a través de la recolección de muestras en los puntos de captación (agua cruda) y salida del sistema. Los cálculos analíticos fueron realizados por el Laboratorio de Servicios Analíticos Químicos y Microbiológicos en agua y Alimentos (SAQMIC) basándose en el procedimiento de análisis de las Normas APHA-AWWA-WPCF. Los análisis determinaron que en la captación se encontraron coliformes (CT= 1160 UFC/100ml y CF=180 UFC/100ml), pH (6,41), Nitritos (0,090mg/L) y Fosfatos (4,950mg/L), esto debido a que la fuente de captación no presenta ningún tipo de protección, alrededor de la toma de agua se realiza actividades antropogénicas como ganadería y agricultura; en la salida del sistema se evidencia coliformes (CT= 1858 UFC/100ml y CF= 138 UFC/100ml), color (22 Und Co/Pt), Nitritos (0,015mg/L), Fosfatos (3,520mg/L), en el sistema actual existe un estancamiento de agua en un tanque Imhoff, determinándose que estos parámetros se encuentran fuera de la Norma Técnica Ecuatoriana INEN 1108: 2011. Para el mejoramiento de la calidad del agua en el nuevo diseño, se enfoca en la eliminación de materiales sólidos y eliminación de agentes patógenos, el cual consta de un desarenador, un sistema de filtración, aireación y desinfección, lo que garantizará la calidad del agua, por lo que se recomienda realizar muestreos periódicos del agua que se consume y mantener un registro que permita el monitoreo de la calidad del agua.es_ES
dc.description.abstractThis research aimed to redesign the System Drinking Water Treatment of Linares Parish, Chaco Cantón, in order to improve water quality and life of the population. An inspection of the current system of treatment was carried out to identify potential system failures, then a chemical and microbiological physical characterization was performed using a simple sampling through samples collection at collections points (water raw) and system output. Analytical calculations were performed by the Laboratory of Analytical Services Chemical and Microbiological Water and food (SAQMIC) based on the method of analysis of APHA_AWWA _ WPCF Standards: The analysis determined that the uptake coliforms (CT = 1160 CFU/ 100ml met and CF = 180 CFU / 100ml), pH (6.41), nitrites (0,090mg / L) and Phosphates (4,950mg / L) because of the source of resources doesn´t have any protection, about water intake is carried out anthropogenic activities such as livestock and agriculture; in the system output coliforms (CT = 1858 CFU / 100ml and CF = 138 CFU / 100ml), Color (22 Und Co / Pt), Nitrites (0,015mg / L), Phosphates (3,520mg / L), in the current system there is a stagnation of water in an Imhoff tank, determined that these parameters are outside the Ecuadorian Technical Standard INEN 1108: 2011. In order to improve water quality in the new design, it focuses on removing materials solid and elimination of pathogens, which consist of a sand trap, a filtration system, aeration and disinfection, ensuring water quality, so it is recommended periodic sampling of water consumed and maintain a register of monitoring water quality.es_ES
dc.language.isospaes_ES
dc.publisherEscuela Superior Politécnica de Chimborazoes_ES
dc.relation.ispartofseriesUDCTFC;236T0231-
dc.rightsinfo:eu-repo/semantics/openAccesses_ES
dc.subjectTECNOLOGÍA Y CIENCIAS DE LA INGENIERÍAes_ES
dc.subjectBIOTECNOLOGÍAes_ES
dc.subjectTRATAMIENTO DE AGUA POTABLEes_ES
dc.subjectCARACTERIZACIÓN FÍSICO-QUÍMICO Y MICROBIOLÓGICAes_ES
dc.subjectREDISEÑO DE PLANTA DE TRATAMIENTOes_ES
dc.subjectEL CHACO (CANTÓN)es_ES
dc.titleRediseño de la planta de tratamiento de agua potable para la parroquia Linares, cantón El Chaco.es_ES
dc.typebachelorThesises_ES
dc.contributor.miembrotribunalLeón Chimbolema, José Gerardo-
dc.rights.urihttps://creativecommons.org/licenses/by-nc-sa/3.0/ec/es_ES
Aparece en las colecciones: Ingeniero/a en Biotecnología Ambiental; Ingeniero/a Ambiental

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
236T0231.PDF7,4 MBAdobe PDFVista previa
Visualizar/Abrir


Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons Creative Commons