Por favor, use este identificador para citar o enlazar este ítem:
http://dspace.espoch.edu.ec/handle/123456789/2511
Registro completo de metadatos
Campo DC | Valor | Lengua/Idioma |
---|---|---|
dc.contributor.advisor | Andrade, Mónica | - |
dc.contributor.author | Armas Altamirano, Graciela Lorena | - |
dc.date.accessioned | 2013-07-18T17:24:57Z | - |
dc.date.available | 2013-07-18T17:24:57Z | - |
dc.date.issued | 2013-07-18T17:24:57Z | - |
dc.identifier.citation | Armas Altamirano, Graciela Lorena. (2013). Diseño de un sistema de tratamiento de agua residual para la Tenería Neogranadina S.A. de la ciudad de Ambato. Escuela Superior Politécnica de Chimborazo. Riobamba. | es_ES |
dc.identifier.uri | http://dspace.espoch.edu.ec/handle/123456789/2511 | - |
dc.description | Se diseñó un sistema de tratamiento de agua residual para la Tenería Neogranadina S.A. de la ciudad de Ambato para las aguas provenientes de los procesos de carnaza y de recurtición, tintura y engrase. La tesis tiene un carácter experimental, utilizando como procesos lógicos la inducción ya que se partió de la observación de los procesos desarrollados en la empresa., para posteriormente realizar un diagnóstico para así tomar muestras en envases plásticos con capacidad para 5 litros y datos relevantes en el lugar de muestreo como pH y temperatura. Al caracterizar el agua residual proveniente de las diferentes etapas de la Tenería Neogranadina S.A., los resultados fueron, 1101 mg/L de DQO, 14,28 mg/L de sulfuros, 840 mg/L de DBO5, 760 mg/L SS, 9526 ml/L de MES, los cuales fueron analizados y tratados con el fin de bajar el nivel de contaminación, puesto que no cumple con los límites de descarga establecidos en el Texto unificado de legislación ambiental secundaria, anexo VI, tabla 9. Además la empresa, mediante la implementación de este sistema de tratamiento, logrará reducir la carga contaminante por debajo de los límites establecidos por la normativa vigente. Se puede indicar, que como resultado del tratamiento del agua residual, se obtuvo una remoción del DQO del 91%, DBO595%, para el contenido de sulfuro se tiene un porcentaje de reducción del 99,9%. La reducción de los sólidos en suspensión del 94%. Y una remoción de fenoles del 99%. Obteniéndose de esta manera un agua tratada que puede ser descargada al alcantarillado público, puesto que cumple con los límites de descarga La empresa deberá hacer análisis frecuentes al agua tratada para verificar que el tratamiento está marchando bien y que los contaminantes están siendo minimizados. | es_ES |
dc.description.abstract | A wastewater treatment system was designed for Tenería Neogranadina S.A. in the city of Ambato for the water coming from the fleshing, retanning, dyeing and greasing processes. The thesis has an experimental character, using induction as a logical process, since it started from the observation of the processes developed in the company, to later carry out a diagnosis in order to take samples in plastic containers with a capacity of 5 liters and relevant data in the sampling place, such as pH and temperature. When characterizing the wastewater from the different stages of Tenería Neogranadina S.A., the results were 1101 mg/L of COD, 14.28 mg/L of sulfides, 840 mg/L of BOD5, 760 mg/L of SS, 9526 ml/L of MES, which were analyzed and treated in order to lower the level of contamination, since it does not comply with the discharge limits established in the Unified Text of Secondary Environmental Legislation, Annex VI, Table 9. In addition, by implementing this treatment system, the company will be able to reduce the pollutant load below the limits established by current regulations. As a result of the wastewater treatment, the COD was removed by 91%, the BOD by 595%, and the sulfur content was reduced by 99.9%. The reduction of suspended solids was 94%. And a phenol removal of 99%. This results in treated water that can be discharged into the public sewer, since it complies with the discharge limits. The company must perform frequent analyses of the treated water to verify that the treatment is working properly and that the contaminants are being minimized. | es_ES |
dc.language.iso | spa | es_ES |
dc.publisher | Escuela Superior Politécnica de Chimborazo | es_ES |
dc.relation.ispartofseries | UDCTFC;96T00193 | - |
dc.rights | info:eu-repo/semantics/openAccess | es_ES |
dc.subject | AGUAS RESIDUALES | es_ES |
dc.subject | SISTEMAS DE TRATAMIENTO DE AGUAS RESIDUALES | es_ES |
dc.subject | DISEÑO DE SISTEMAS DE TRATAMIENTO DE AGUAS RESIDUALES | es_ES |
dc.subject | DISMINUCIÓN DE LA CONTAMINACIÓN | es_ES |
dc.title | Diseño de un sistema de tratamiento de agua residual para la Tenería Neogranadina S.A. de la ciudad de Ambato | es_ES |
dc.type | bachelorThesis | es_ES |
dc.contributor.miembrotribunal | Ávalos, César | - |
dc.rights.uri | https://creativecommons.org/licenses/by-nc-sa/3.0/ec/ | es_ES |
Aparece en las colecciones: | Ingeniero/a Químico/a |
Ficheros en este ítem:
Fichero | Descripción | Tamaño | Formato | |
---|---|---|---|---|
96T00193.pdf | 6,92 MB | Adobe PDF | Visualizar/Abrir |
Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons